Link Line Tap
Brand Name: Clipsal
Type: Plain
Conductor Size: 35 sq-mm
Length: 35 mm
Material: Brass
Clipsal Line Tap Link Suit 35Mm2 Cable - BP24
This item is currently available for backorder with an estimated arrival time of 2 days
Please note this ETA is provided to us by our suppliers and could potentially be delayed due to factors outside our control. If there are any delays we will contact you to keep you updated.
Choose your style, Select your Switch and Checkout
We can customise your powerpoint to a range of colours and layouts, suited to your needs.

SKU | CLIBP24 |
---|---|
Supplier No | BP24 |
EAN / Barcode | 9318793001991 |
Width | 25 |
Height | 34.000000 |
Length | 24.000000 |
Width | 25.000000 |
Brand | Clipsal |
Range | Max4 |
Material | Brass |
Get Max 4 your buck
Complete protection with high performance. With Clipsal Max 4 you will find a range of enclosures, switchboards, residual current devices, miniature circuit breakers, isolators, distribution boards, overvoltage protection and accessories.
A FEW FAQS
Issue: Difference between the P24 and +24 terminals on the ATV630 drives. Product Line: ATV630 Environment: All serial numbers Cause: N/A Resolution: P24 Output power supply for digital inputs and STO +24 Vdc Tolerance: -15...+20% Current: maximum 1.1 A +24 Digital input power supply +24 Vdc input supply Tolerance: -15...+20% Current: 100 mA
Issue : Maximum current, P24 external supply? Product Line : Altivar Machines, Altivar 340 Environment : All models and serial number Cause : N/A Resolution : The P24 terminal is only available on the Frame Size 4 and 5 drives, ATV340D30N4 to ATV340D75N4 Max current is 0.8 A Tolerance is minimum 19VDC and maximum 30VDC Information is listed from the ATV340 Installation Manual NVE61069
Issue: Give a "Run Forward" Command when in 2 wire control. Product Line: All current production models of Altivar drives. Environment: All current production models of Altivar drives, all serial numbers. Cause: Customer is sending a run forward command via the terminals but the drive stays in Rdy status. Resolution: A "Run Forward" command is issued on the terminals by closing a connection between +24V terminal (P24 on the ATV212) to the LI1 terminal (F on the ATV212). Note that other programmed functions or conditions (freewheel stop, run permissive, active fault code) can prevent the drive from running when this signal is connected.' You can use an external 24v and LI1 for the hot wire and 0V for your neutral. (F terminal for the hot wire to CC terminal for the neutral for ATV212)
Issue: Programming an ATV320 using an external 24Vdc source Product line: Altivar 320 Environment: External 24v Cause: Need power the ATV320 with external 24Vdc so that it can be programmed Resolution: Yes, an external 24Vdc can be provided to the ATV320 in order to power up the display and program the drive. To connect an external 24VDC supply to the ATV320, the P24 terminal must be used. The P24 is an input and output: - When there is no external supply connected to this terminal, the P24 is an output and delivers 24VDC to the STO circuit. - When there is an external supply connected to this terminal, the P24 is an input and the drive is supplied by the external supply. The +24 terminal is used to provide 24VDC to the drive digital inputs. +24 is not designed to be used as an input to supply the control block.
Issue: ATV32 power up with an external 24Vdc supply Product Line: ATV32 Environment: All serial numbers Cause: To maintain control power to the drive. Resolution: Yes, the P24 terminal and COM are the connections that can be used for external 24VDC. **NOTE: This does not apply to the ATV320, the P24 terminal on ATV320 is only used to supply the STO (Safe Torque Off) terminal, P24 will not accept 24v.
Issue: External power supply connection Product Line: ATV630 Environment: All models and serial numbers Cause: None Resolution: The external +24vdc power supply must be connected to terminals P24 and 0v. The positive is P24 and the negative is 0v. DO NOT connect the external power supply to +24v.